Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: Outdoor sensor requirement

Updated · by Aurora Star Tech Inc.

Outdoor sensor requirement on a Weil-McLain boiler: The outdoor sensor supplied with the boiler must be installed unless one of the listed exemptions applies.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec 80/110/150/199 Series 3

How to fix outdoor sensor requirement: step by step

  1. Install the supplied outdoor sensor.
  2. Only skip it if an exemption in the manual applies.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More commissioning tips for boiler

Source: ECO Tec Series 3 boiler manual, p. 184. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977