Weil-McLain Boiler: Multi-boiler RS485 wiring

Updated · by Aurora Star Tech Inc.

Multi-boiler RS485 wiring on a Weil-McLain boiler: Boilers communicate over a shielded 3-wire RS485 bus. The Unity 2.0 boiler must be the Master.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Evergreen 110/155/220/299/300/399 multi-boiler installs

How to fix multi-boiler rs485 wiring: step by step

  1. Use shielded 3-wire cable, no longer than 1,000 feet.
  2. Connect Boiler-to-Boiler OUT (JP4 GND, B2, A2) on one boiler to Boiler-to-Boiler IN (JP4 GND, B3, A3) on the next.
  3. Continue until all boilers are interconnected.
  4. Install the drain line to proper ground on the Master boiler only. Do not ground on both the Master and the final boiler.
  5. Do not return the last boiler's wires to the Master's A3/B3/GND ports. This creates a communication loop.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 55. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977