Weil-McLain Boiler: Multi-boiler RS485 wiring
Multi-boiler RS485 wiring on a Weil-McLain boiler: Boilers communicate over a shielded 3-wire RS485 bus. The Unity 2.0 boiler must be the Master.
Applies to: Evergreen 110/155/220/299/300/399 multi-boiler installs
How to fix multi-boiler rs485 wiring: step by step
- Use shielded 3-wire cable, no longer than 1,000 feet.
- Connect Boiler-to-Boiler OUT (JP4 GND, B2, A2) on one boiler to Boiler-to-Boiler IN (JP4 GND, B3, A3) on the next.
- Continue until all boilers are interconnected.
- Install the drain line to proper ground on the Master boiler only. Do not ground on both the Master and the final boiler.
- Do not return the last boiler's wires to the Master's A3/B3/GND ports. This creates a communication loop.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.