Weil-McLain Boiler: Select a DHW circulator for direct-connected piping
Select a DHW circulator for direct-connected piping on a Weil-McLain boiler: Add the boiler pressure drop, the piping pressure drop and the water heater pressure drop to get the total head. Then pick a circulator that delivers the required flow at that head.
Applies to: Combined space heating and DHW systems with direct-connected DHW piping
How to fix select a dhw circulator for direct-connected piping: step by step
- Get the required boiler water flow rate (GPM) at 190 F and the water heater pressure drop at that flow (feet of water) from the heater data.
- Find the boiler model in the pressure drop figure and pick the first flow rate at or above the required flow.
- Read the boiler pressure drop (H1) and piping pressure drop (H2) from that row, using the copper pipe size listed.
- Add H1, H2 and H3 (water heater drop) to get the total head.
- Select a circulator that delivers the required GPM against the total head.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.