Weil-McLain Boiler: Install the relief valve and discharge line
Install the relief valve and discharge line on a Weil-McLain boiler: The relief valve mounts in a 3/4 in. street elbow on the boiler supply tee. The discharge line must be installed to protect people and property from hot water or steam discharge.
Applies to: All Ultra Series 4 models
How to fix install the relief valve and discharge line: step by step
- Install the relief valve in the 3/4 in. street elbow piped from the boiler supply tee. Pipe it only as shown in the manual.
- Connect the discharge piping to a safe disposal point. Keep it as short as possible and the same size as the valve outlet along its whole length.
- Pitch the discharge line downward from the valve. End it at least 6 in. above a floor drain where discharge is visible.
- End the discharge line plain, not threaded, using material rated for 375 °F or higher.
- Do not route the discharge where freezing can occur. Do not place a shutoff valve between the relief valve and boiler or in the discharge line. Do not plug or obstruct the discharge line.
- After filling and pressurizing, lift the lever to test the valve. Confirm it discharges freely. Replace the valve if it does not operate correctly.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.