Weil-McLain Boiler: 0-10 VDC remote modulation input
0-10 VDC remote modulation input on a Weil-McLain boiler: A 0-10 VDC signal can be used for remote modulation. It uses the INPUT 2 heat demand, so the same input cannot be used for a dry contact. The remote target and remote modulation inputs cannot both be used on the same control.
Applies to: ECO Tec Series 3 80/110/150/199
How to fix 0-10 vdc remote modulation input: step by step
- Wire the 0-10 VDC input positive to J16 terminal 6 and common to J16 terminal 5.
- Do not wire any device to INPUT 2 when remote modulation is used.
- If Indirect DHW is needed, connect the DHW aquastat to INPUT 3 or INPUT 4 and assign it to PRIORITY 2.
- Assign INPUT 2 to PRIORITY 3 for the space heating system to be modulated. Accept the defaults for INPUT 2 during the WIZARD.
- After the WIZARD, go to SYSTEM SETTINGS, INPUT USAGE, and change the INPUT 2 SOURCE to 0-10V (default is TT1).
- Check that the boiler turns on at 0.9 VDC and off at 0.5 VDC. These thresholds are fixed and cannot be adjusted.
- Confirm OUTPUT 2 (120VAC) switches on and off with the heat demand.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 73. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.