Weil-McLain Boiler: Zoning three space heating zones with circulators (no DHW)
Zoning three space heating zones with circulators (no DHW) on a Weil-McLain boiler: Factory defaults assign all three inputs to Priority 2 and fit a three-zone circulator system.
Applies to: SVF Series 1 with Unity control and circulator zoning
How to fix zoning three space heating zones with circulators (no dhw): step by step
- Review the 120VAC output wiring (p. 49) and 24VAC input wiring (p. 59).
- Wire the thermostats to P11-4/5, P15-1/2 and P15-3/4. Wire the circulators to P2.
- Choose the space heating system type in the Wizard or in the Priority 2 menu.
- Keep the factory defaults for the system type unless a change is needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 1500-3000 Series 1 boiler manual, p. 66. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.