Weil-McLain Boiler: Boiler and system circulator relay requirement
Boiler and system circulator relay requirement on a Weil-McLain boiler: An external relay with external power is required for the boiler circulator when its load exceeds 2.2 A FLA, 3.6 A locked rotor, or 16.4 A inrush. An external relay is also required for a system circulator above 2.0 A FLA.
Applies to: Boiler and system circulators in multi-boiler installs
Common causes of boiler and system circulator relay requirement
- Boiler circulator load above 2.2 A FLA
- Boiler circulator locked rotor above 3.6 A
- Boiler circulator inrush above 16.4 A
- System circulator load above 2.0 A FLA
How to fix boiler and system circulator relay requirement: step by step
- Check the boiler circulator FLA, locked rotor and inrush against the limits.
- Check the system circulator FLA against the 2.0 A limit.
- If any limit is exceeded, provide an external relay and external power to that circulator.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 27 (also p. 32). Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.