Weil-McLain Boiler: Determine if water treatment is needed and clean the system
Determine if water treatment is needed and clean the system on a Weil-McLain boiler: Petroleum-based cleaning or sealing compounds must not be used in the boiler system. Leaks must be eliminated because continual fresh makeup water shortens boiler life. Sediment must be flushed out before the boiler is connected.
Applies to: Water boiler system preparation
Common causes of determine if water treatment is needed and clean the system
- Sediment in the system affecting chemical treatment or damaging components
- Continual fresh makeup water causing mineral buildup and cast iron overheating
- Water that is very hard (above 7 grains) or low pH (below 7)
How to fix determine if water treatment is needed and clean the system: step by step
- Flush the whole system without the boiler connected until the water runs clean.
- On zoned systems, flush each zone separately through a purge valve; install purge and isolation valves if missing.
- Verify water chemistry; consult a water treatment company for very hard or low-pH water.
- Keep boiler water pH between 7.0 and 8.5.
- Eliminate all system leaks.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.