Weil-McLain Boiler: Direct exhaust: combustion air from boiler room
Direct exhaust: combustion air from boiler room on a Weil-McLain boiler: Direct exhaust boilers draw combustion air from the boiler room through openings to outside or to other spaces, so the room must not have contaminated air.
Applies to: Ultra boilers, direct exhaust sidewall or vertical
Common causes of direct exhaust: combustion air from boiler room
- Contaminated air in the boiler room
- Exhaust fans creating negative pressure in the room
- Undersized air openings when other appliances share the space
How to fix direct exhaust: combustion air from boiler room: step by step
- Check that the boiler room will not contain contaminated air before using room air.
- Size combustion air openings for all appliances in the room, including exhaust fans and air movers.
- Make sure the room is not under negative pressure unless all appliances are direct vent.
- Count louver and grille reduction when sizing openings (free area).
- Follow Figure 96 sizing and the Massachusetts instructions on page 65 when they apply.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 83-84. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.