Weil-McLain Boiler: Build separate-pipe vertical and sidewall terminations
Build separate-pipe vertical and sidewall terminations on a Weil-McLain boiler: Terminations use bird screens (bought separately) and fixed dimensions. Air intake and vent outlet must face the right way and sit at the right height.
Applies to: Separate vent and air pipe terminations
How to fix build separate-pipe vertical and sidewall terminations: step by step
- Fit bird screens into the vent termination elbow and air termination elbow. Screens are sold separately; see the parts list.
- On Ultra-230 with 3 in piping, cut the 4 in bird screen by using the 3 in fitting as a template.
- End the air pipe in a down-turned 180-degree return bend. The air intake edge must be at least 12 in above roof or snow line.
- End the vent pipe in an up-turned coupling so flue products do not recirculate into the combustion air.
- Hold the finished termination dimensions shown in Figure 22, page 23.
- Do not extend exposed vent pipe outside the building beyond what the drawings show, because condensate can freeze and block it.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.