Weil-McLain Boiler: Multiple boiler placement and wall-mount spacing
Multiple boiler placement and wall-mount spacing on a Weil-McLain boiler: Clearance and spacing for side-to-side, back-to-back and wall-mounted Ultra boilers.
Applies to: Ultra models 80–399 in multiple boiler rooms
How to fix multiple boiler placement and wall-mount spacing: step by step
- Use the side-to-side (Figure 56) or back-to-back (Figure 57) layout, or wall mount (Figure 58).
- Keep the indicated access clearances. If not possible, use at least the minimum clearances on page 5 and follow local codes.
- Build a foundation if the floor is uneven or flooding is possible, sized to the spacing shown.
- For wall-mounted boilers, leave about 6 inches between boilers so the jacket door can be removed.
- Verify the wall can carry the structural load (see page 50).
- Keep a minimum 30-inch walkway or follow local code.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.