Weil-McLain Boiler: Indirect DHW aquastat wiring for priority

Updated · by Aurora Star Tech Inc.

Indirect DHW aquastat wiring for priority on a Weil-McLain boiler: Heat only and combi models use different inputs for indirect DHW.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 heat only and combi models

How to fix indirect dhw aquastat wiring for priority: step by step

  1. Heat only: connect the DHW aquastat to any one of the four input and output pairs. Assign it to PRIORITY 1 in the WIZARD or System Settings menu.
  2. Combi: connect the DHW aquastat to Input 2 or Input 3. Assign it to PRIORITY 2 in the WIZARD or System Settings menu.
  3. On combi, the internal combi DHW is PRIORITY 1 and the indirect tank is PRIORITY 2.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 68-69. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.