Weil-McLain Boiler: Check venting system operation (monthly in heating season)
Check venting system operation (monthly in heating season) on a Weil-McLain boiler: Check the vent system at least once a month during the heating season while the boiler is firing. A proper draft keeps the flame steady when a test flame is held near the vent.
Applies to: EG and PEG Series 7 boilers with draft hood
Common causes of check venting system operation (monthly in heating season)
- Obstructed flue or vent
- Exhaust fans or other equipment in the boiler room pulling air
- Other causes of improper venting
How to fix check venting system operation (monthly in heating season): step by step
- With the boiler firing, hold a lit candle or match just below the lower edge of the draft hood skirt.
- If the flame burns undisturbed, the vent system is working properly.
- If the flame blows out or flickers strongly, inspect the vent system for obstructions and other causes of improper venting, such as exhaust fans in the boiler room.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.