Expansion tank check on a Weil-McLain boiler: Check the expansion tank when the relief valve weeps often or the pressure rises too high on heat-up.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra Series 4 boilers, hydronic system

Common causes of expansion tank check

  • Closed-type tank waterlogged
  • Diaphragm or bladder tank undersized or membrane damaged
  • Automatic air vents used with a closed-type tank

How to fix expansion tank check: step by step

  1. Identify tank type: open, closed (air cushion) or diaphragm/bladder.
  2. Open type: confirm it is above the highest radiator or baseboard and the gauge glass and overflow are working.
  3. Closed type: confirm a tank fitting such as B&G Tank-Trol or Taco Taco-Trol is installed. Do not use automatic air vents with closed-type tanks.
  4. If the relief valve weeps often on a closed tank, check the fill level. If correct, check tank size against manufacturer data and replace with a larger tank if needed.
  5. Diaphragm or bladder type: check tank size for the system. Add tanks if too small.
  6. If size is adequate, remove the tank and check charge pressure (usually 12 psig residential). If it will not hold pressure, the membrane is damaged. Replace the tank.
  7. Systems with diaphragm or bladder tanks need at least one automatic air vent, preferably on top of an air eliminator.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 gas-fired water boiler manual, p. 111. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.