Weil-McLain Boiler: Check flame signal
Check flame signal on a Weil-McLain boiler: Read the flame signal in Diagnostics/Inputs. It must be at least 20 above the shutdown value for the model (Figure 119).
Applies to: Ultra 80, 105, 155, 230, 299, 399
Common causes of check flame signal
- Fouled ignitor
- Damaged ignitor insulation
- Poor ground path to the ignitor
- Vent/air piping or heat exchanger problem if the signal stays low
How to fix check flame signal: step by step
- Go to Diagnostics/Inputs on the U-Control display (see Figure 115, page 102).
- Confirm the flame signal is at least 20 above the Figure 119 shutdown value.
- If the signal falls below that, the U-Control raises the firing rate to recover it.
- If the signal is low, clean the ignitor. If it does not improve and the ground wiring and continuity are good, replace the ignitor.
- If the signal is still low, inspect the vent and air piping, then the heat exchanger, and clean it if needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 gas-fired water boiler manual, p. 112-113. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.