Weil-McLain Boiler: Check burner flame at high and low fire
Check burner flame at high and low fire on a Weil-McLain boiler: Visual flame check through the observation window, then combustion check with instruments.
Applies to: SVF 1500-3000 Series 1 boiler
How to fix check burner flame at high and low fire: step by step
- Inspect the flame through the observation window.
- At high fire, the flame should be blue and stable, with the burner surface covered in orange dots.
- At low fire, the flame should be stable, evenly spread over the burner surface and a uniform orange.
- Perform the combustion check with instruments (see startup procedure, page 88).
- If the flame is unsatisfactory or combustion cannot be adjusted within the values in Figure 80, shut down, let the boiler cool, and service the burner.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF Series 1 boiler manual, p. 96. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.