Weil-McLain Boiler: Inspect ignition electrode and flame sense rod
Inspect ignition electrode and flame sense rod on a Weil-McLain boiler: Clean or replace the electrode and check the ignition wiring.
Applies to: SVF 1500-3000. SVF 1500/2000 use a male spade for flame sense; SVF 2500/3000 use a female spade.
Common causes of inspect ignition electrode and flame sense rod
- White oxide buildup on electrode or flame sense rod
- Damaged gasket or harness
How to fix inspect ignition electrode and flame sense rod: step by step
- Remove the ignition electrode from the combustion chamber.
- Clean oxides from the electrode and flame sense rod with steel wool.
- If the electrode cannot be cleaned, replace it.
- Replace the gasket if worn and reinstall it correctly positioned.
- Confirm the ground wire is on the spade connection.
- Inspect the flame sense harness and connections. Replace if needed.
- Check ignition cable resistance; a good cable reads 900 to 1000 ohms.
- Check ground continuity from the electrode to the ground terminal strip and replace bad ground wires.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 95. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.