Weil-McLain Boiler: Check temperature sensors with an ohmmeter
Check temperature sensors with an ohmmeter on a Weil-McLain boiler: Compare sensor resistance against the reference table.
Applies to: Boiler In, Boiler Out, DHW Out, Flue, Outdoor and System Supply/Return sensors
Common causes of check temperature sensors with an ohmmeter
- Open or shorted sensor wiring or a failed sensor.
How to fix check temperature sensors with an ohmmeter: step by step
- Measure sensor resistance at 32 F, 60 F, 70 F and 212 F (ice point, room temperature and boiling point).
- Compare readings with the sensor resistance table.
- For a control check, connect a resistance decade box in place of the sensor and confirm the display temperature matches the input resistance.
- For dual sensors, confirm the two temperatures are within 10 F.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 160. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.