Weil-McLain Boiler: Concentric termination: piping supports and slope
Concentric termination: piping supports and slope on a Weil-McLain boiler: Support the vent and air piping so the weight does not rest on boiler fittings. Pipe must be supported well enough that the termination cannot slip or move. Clamps must not cut into the pipe.
Applies to: Sidewall and vertical 3 in or 4 in concentric termination
How to fix concentric termination: piping supports and slope: step by step
- Install pipe supports at least every 5 ft on horizontal and vertical runs.
- Install a hanger within 6 in of any upturn in the piping.
- Slope horizontal piping down toward the boiler at least 1/4 in per foot.
- Rotate the concentric Y-fitting about 30 degrees so pipe centers match those at the boiler.
- Install the concentric termination before running piping from the boiler to it.
- Do not drill or screw into the vent or air pipe.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 74, 76-77. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.