Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: Concentric termination: piping supports and slope

Updated · by Aurora Star Tech Inc.

Concentric termination: piping supports and slope on a Weil-McLain boiler: Support the vent and air piping so the weight does not rest on boiler fittings. Pipe must be supported well enough that the termination cannot slip or move. Clamps must not cut into the pipe.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Sidewall and vertical 3 in or 4 in concentric termination

How to fix concentric termination: piping supports and slope: step by step

  1. Install pipe supports at least every 5 ft on horizontal and vertical runs.
  2. Install a hanger within 6 in of any upturn in the piping.
  3. Slope horizontal piping down toward the boiler at least 1/4 in per foot.
  4. Rotate the concentric Y-fitting about 30 degrees so pipe centers match those at the boiler.
  5. Install the concentric termination before running piping from the boiler to it.
  6. Do not drill or screw into the vent or air pipe.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 boiler manual, p. 74, 76-77. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair