Weil-McLain Boiler: No space heating in mild weather, display shows WWSD
No space heating in mild weather, display shows WWSD on a Weil-McLain boiler: Warm weather shutdown blocks space heating when the outdoor temperature is above the WWSD setting. The boiler sits in standby and the display shows WWSD. DHW and Custom priorities are not blocked.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
Common causes of no space heating in mild weather, display shows wwsd
- Outdoor temperature is above the WWSD setting
- Outdoor sensor reading is off
How to fix no space heating in mild weather, display shows wwsd: step by step
- Compare the outdoor temperature on the boiler information screen with WWSD Temp in Boiler Settings.
- Lower WWSD or set it to OFF if the customer needs heat at that temperature.
- WWSD needs the outdoor sensor. Without a sensor, WWSD must be OFF.
- If the outdoor reading looks wrong, use Adjust Outdoor in Boiler Settings to calibrate it.
- Check the sensor mounting: outside wall, out of direct sun and away from other heat or cooling, wire outlet pointing down.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - WWSD, p.3; Boiler Settings, p.58; Field wiring E, p.13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.