Weil-McLain Boiler: Clean the heat exchanger flue side interior
Clean the heat exchanger flue side interior on a Weil-McLain boiler: Remove the control circuit board first so water does not reach it. Use a strong light to confirm the flue ways are clear. Do not use any solvent on the exchanger. Use water only if a vacuum cannot clean it fully.
Applies to: ECO Tec Series 3 boilers
Common causes of clean the heat exchanger flue side interior
- Accumulated deposits on the heating surfaces
- Insulation pieces that fell into the exchanger
- Lint or sediment blocking the flue ways
How to fix clean the heat exchanger flue side interior: step by step
- Label and disconnect all connectors and harnesses from the circuit board, remove its four screws and snap-fit standoffs, and set the board aside.
- Use a strong light to check that the flue ways are clear and unobstructed.
- Use a vacuum to remove deposits and any insulation pieces from the heating surfaces. Do not use solvent.
- If the vacuum cannot clean it fully, place a shallow pan under the condensate tube connection.
- Loosen the condensate hose clamp and slide the trap off the drain connection (see page 63).
- Spray fresh water into the heat exchanger and tubes to remove sediment, collecting the water in the pan.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 151. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.