Weil-McLain Boiler: Provide room air openings
Provide room air openings on a Weil-McLain boiler: Air opening rules depend on whether the Ultra is alone in the boiler room or shares the space with other gas or oil appliances.
Applies to: Ultra Series 4 boilers
How to fix provide room air openings: step by step
- If the boiler is alone and clearances are at least the service clearances in Figure 1, no room openings are needed.
- If clearances are smaller, provide two openings. Each must have 1 sq in free area per 1,000 Btuh of boiler input.
- If other appliances share the space, size the openings for those appliances using the National Fuel Gas Code or CAN/CSA B149.1 and B149.2. The Ultra needs no added opening area because it is direct vent.
- Reinstall the boiler jacket front door after service and make sure it is secured.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 4 gas-fired water boiler manual, p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.