Weil-McLain Boiler: Gas valve adjustment at low fire
Gas valve adjustment at low fire on a Weil-McLain boiler: Adjust low fire only after confirming low fire RPM.
Applies to: ECO Tec Series 3 80/110/150/199
How to fix gas valve adjustment at low fire: step by step
- Force LOW fire and let the boiler stabilize.
- Confirm the RPM against the table in Figure 125, 126 or 127.
- Remove the 4 mm Allen cap to reach the offset screw.
- If CO2 is high, turn the offset screw counter-clockwise in small steps.
- If CO2 is low, turn the offset screw clockwise in small steps.
- Continue until target CO2 is reached and confirm CO is within limits.
- Reinstall the 4 mm cap.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.