Annual service inspection on a Weil-McLain boiler: Service technician inspection done at the start of each heating season, before start-up.
Applies to: EG and PEG Series 7 boilers
Common causes of annual service inspection
- Reported problems
- Blocked air openings or vent
- Leaks, soot or scale
How to fix annual service inspection: step by step
- Inspect and correct any problems reported by the owner before proceeding.
- Confirm the boiler area is free of combustible materials, flammable vapors and contaminants listed on page 12. Remove contaminants or pipe in combustion air per code.
- Confirm the combustion and ventilation air openings are open and unobstructed. Check automatic combustion air dampers, if used, for operation and wiring.
- Visually inspect the flue gas vent for blockage, deterioration or leakage. Repair leaking joints per the vent maker's instructions.
- Confirm masonry chimneys are lined in good condition with no openings into the chimney.
- Check the pilot and main burner flames (see page 63).
- Check the boiler interior and system piping for leaks and repair them. Do not use petroleum-based cleaning or sealing compounds.
- Inspect the boiler flue collector and heating surfaces with a bright light. If soot is present, clean per the heating surface procedure.
- If rusty scale is present, check that return water temperature is properly maintained.
- Reconnect the vent and draft diverter, and replace all boiler components before returning to service.
- Check inside and around the boiler for leaks and repair the source.
- Inspect the base insulation. If insulation is damaged or displaced, do not operate the boiler until it is replaced or repositioned.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.