Weil-McLain Boiler: Pilot lights but does not energize main gas valve
Pilot lights but does not energize main gas valve on a Weil-McLain boiler: The pilot is lit but the main valve does not come on, usually because the flame signal does not register.
Applies to: EG water boilers
Common causes of pilot lights but does not energize main gas valve
- Flame signal below 60 in control diagnostics
- Pilot flame sense wiring or flame rod faulty
- Low inlet gas pressure with pilot regulator in use
How to fix pilot lights but does not energize main gas valve: step by step
- Check the Pilot Flame Signal in control diagnostics. A signal below 60 is not proven flame.
- If the signal does not register, check the Pilot Flame Sense wiring and the flame rod for continuity and corrosion. Replace the rod if necessary.
- If a pilot gas pressure regulator is used with low inlet pressure, increase the pilot regulator setting to supply more gas to the pilot.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 Boiler Manual, p. 75. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.