Weil-McLain Boiler: Check the derate before setting the boiler
Check the derate before setting the boiler on a Weil-McLain boiler: Vent and air piping length reduces the maximum input. Work out the equivalent length, apply the derate for your model and vent type, and check the input against the site before startup.
Applies to: SVF 1500-3000 boilers
How to fix check the derate before setting the boiler: step by step
- Find the vent/air piping equivalent length in feet.
- Pick the derate formula for the model and vent type (direct exhaust or direct vent).
- Calculate the derate percentage and reduce the maximum input by that amount.
- For elevations above 5,500 ft, follow the high altitude section of the manual for control parameter changes.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: SVF Series 1 boiler manual, p. 120. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.