Weil-McLain Boiler: Gas valve adjustment at high fire
Gas valve adjustment at high fire on a Weil-McLain boiler: Only a qualified technician with calibrated combustion instruments should adjust the valve.
Applies to: ECO Tec Series 3 80/110/150/199
Common causes of gas valve adjustment at high fire
- Difficulty igniting
- Poor flame stability at low fire
- Combustion noise
- High carbon monoxide
How to fix gas valve adjustment at high fire: step by step
- Set MAX RATE and MIN RATE for the priority being tested to 100% and 10%.
- Go to DIAGNOSTICS, Manual test mode, and force HIGH fire.
- Confirm blower speed reaches the RPM in Figure 125, 126 or 127.
- Read CO2 and CO and allow the analyzer to stabilize.
- If CO2 is high, turn the throttle screw clockwise in small steps.
- If CO2 is low, turn the throttle screw counter-clockwise in small steps.
- Continue until the target CO2 is reached and confirm CO is within limits.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 135-136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.