Weil-McLain Boiler: Inserting PVC or ABS vent or air pipe into boiler connector
Inserting PVC or ABS vent or air pipe into boiler connector on a Weil-McLain boiler: Seal comes from the internal gasket, so the clamp only holds the pipe in place.
Applies to: Boiler vent connector and air pipe connector
Common causes of inserting pvc or abs vent or air pipe into boiler connector
- Rough or unchamfered pipe end damages the adapter gasket
- Pipe not inserted to the mark
- Clamp overtightened or adapter bent
How to fix inserting pvc or abs vent or air pipe into boiler connector: step by step
- Clean and chamfer the insertion end of the pipe and deburr its inside.
- Check the adapter for obstructions or foreign objects.
- Loosen the adapter clamp screw.
- Measure 3-1/2 inches from the pipe end and mark it.
- Apply a small amount of silicone grease to the pipe end.
- Insert the pipe into the adapter and slide it down to the 3-1/2 inch mark.
- Tighten the clamp securely but do not overtighten.
- Do not bend the adapter or pipe or force the insertion.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.