Weil-McLain Boiler: Check burner flames
Check burner flames on a Weil-McLain boiler: A proper pilot flame is blue with the inner cone engulfing the pilot flame sensor, and the sensor glows cherry red. A proper main burner flame may show yellow-orange streaks from dust.
Applies to: Spark-ignited pilot and main burners in EG / PEG boilers
Common causes of check burner flames
- Overfired pilot: large flame lifting or blowing past the sensor
- Underfired pilot: small flame with inner cone not engulfing the sensor
- Lack of primary air: yellow flame tip
- Overfired main burners: large flames
- Underfired main burners: small flames
- Lack of primary air at main burners: yellow tipping and sooting
How to fix check burner flames: step by step
- Check that the pilot flame is blue, the inner cone engulfs the pilot flame sensor, and the sensor glows cherry red.
- Check that main burner flames are not large, small or yellow-tipped.
- Correct overfired, underfired or primary air problems before continuing.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.