Weil-McLain Boiler: Remote target setup with 0-10VDC input
Remote target setup with 0-10VDC input on a Weil-McLain boiler: A 0-10VDC signal adjusts the supply target temperature. It replaces the outdoor sensor as the target modifier. The control does not control the target itself.
Applies to: Evergreen 110/155/220/299/300/399
How to fix remote target setup with 0-10vdc input: step by step
- Wire the 0-10VDC positive signal to J16 terminal 6 and the common to terminal 5.
- Wire a heat demand dry contact to an unused input and its pump or valve to the matching output.
- Assign and set up a priority for that input in the Wizard or the contractor menu.
- Set TARGET ADJUST to 0-10V for the priority used for space heating (Priority 2 or 3).
- Set VOLTS FOR MAX TARGET and MAX TARGET TEMP at the voltage that calls for the highest target.
- Set VOLTS FOR MIN TARGET and MIN TARGET TEMP at the voltage that calls for the lowest target.
- Between the two voltages, the target temperature scales in proportion between MAX and MIN TARGET TEMP.
- A dry contact heat demand must be present to start a call for heat.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.