Weil-McLain Boiler: Low water cutoff and high limit requirements

Updated · by Aurora Star Tech Inc.

Low water cutoff and high limit requirements on a Weil-McLain boiler: For ASME or Canadian installs, an external high limit is needed. The boiler has a built-in water temperature and low-water sensor on EG water boilers.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG water boilers

How to fix low water cutoff and high limit requirements: step by step

  1. Install the external high limit in the supply piping between the boiler and the isolation valve.
  2. Set the external high limit at least 20°F above the operating setpoint. The maximum external high limit setting is 240°F.
  3. The maximum operating limit is 210°F.
  4. Install a low water cutoff when the boiler sits above radiation level or when local codes or insurers require it. An extra external LWCO may be used alongside the built-in monitoring.
  5. Wire per page 31.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More commissioning tips for boiler

Source: EG/PEG Series 7 boiler manual, p. 20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.