Weil-McLain Boiler: Verify the remaining appliances on an old common vent
Verify the remaining appliances on an old common vent on a Weil-McLain boiler: Check each appliance still on the old common vent by itself, with all others off, to confirm the vent can carry it safely.
Applies to: Existing common vent after ECO Tec replacement
Common causes of verify the remaining appliances on an old common vent
- Common vent may be oversized for the remaining appliances after the old boiler is removed.
- Blocked, leaking, corroded or poorly pitched vent can cause spillage.
How to fix verify the remaining appliances on an old common vent: step by step
- Seal any unused openings in the common vent.
- Inspect the vent for correct size, horizontal pitch, blockage, restriction, leakage, corrosion or other defects.
- Close building doors and windows and doors to the spaces with appliances on the vent. Run clothes dryers and any non-vented appliance.
- Turn on exhaust fans such as range hoods and bathroom fans to maximum speed. Do not run a summer exhaust fan. Close fireplace dampers.
- Run the appliance being tested with the lighting instructions. Set its thermostat so it runs continuously.
- After 5 minutes of main burner operation, check for spillage at the draft hood relief opening with a match, candle or smoke.
- When the test passes, return doors, windows, fans, dampers and other gas appliances to their original state.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.