Weil-McLain Boiler: Zone circulator relay requirement and wiring limits

Updated · by Aurora Star Tech Inc.

Zone circulator relay requirement and wiring limits on a Weil-McLain boiler: A circulator whose load is above the rated limits must be run through an external relay with its own power supply. The rating values on the page are garbled in the source, so confirm the exact figures from the wiring section of the manual.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 circulator wiring

How to fix zone circulator relay requirement and wiring limits: step by step

  1. Check each circulator's full load amps, locked rotor amps and inrush amps against the limits in the manual.
  2. Provide an external relay and external power to any circulator that exceeds the limits.
  3. For DHW direct piping, confirm the DHW circulator handles the water heater and piping pressure drop.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More other tips for boiler

Source: ECO Tec Series 3 boiler manual, p. 98. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.