Weil-McLain Boiler: Zone valve zoning with direct connection piping (80/110/150 single boiler)
Zone valve zoning with direct connection piping (80/110/150 single boiler) on a Weil-McLain boiler: Use this layout only for zone valve systems that meet the direct connection criteria on page 53. If the system does not qualify, pipe it primary/secondary instead.
Applies to: ECO Tec 80/110/150 single boiler, zone valve direct connection (Figure 65)
How to fix zone valve zoning with direct connection piping (80/110/150 single boiler): step by step
- Confirm the system meets the direct connection criteria on page 53; if not, use primary/secondary piping (pages 58 to 62).
- Install a by-pass pressure regulator (Taco 3196 or equivalent, Item 21) on zone valve systems, unless the circulator has dead-head protection.
- Provide a system expansion tank per the guidelines on page 54 or 57.
- Do not use a closed-type tank if the water heater has an automatic vent.
- For an indirect DHW tank, pipe it as a zone with zone valves so priority works and ghost flows are prevented.
- Wire zone valve end switches to the matching inputs. Use isolation relays for 3-wire end switches.
- Set TARGET MODULATION SENSOR to System Supply on page 123 when system sensors are installed.
- Check that the internal boiler circulator can supply the head and flow in Figure 58, page 48.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.