Weil-McLain Boiler: Check flue gas temperature versus return temperature

Updated · by Aurora Star Tech Inc.

Check flue gas temperature versus return temperature on a Weil-McLain boiler: Flue gas should not run far above the boiler return temperature at high fire.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 gas boilers

Common causes of check flue gas temperature versus return temperature

  • Fouled heat exchanger

How to fix check flue gas temperature versus return temperature: step by step

  1. Set the boiler to high fire.
  2. Use the control display to view flue gas temperature and boiler return temperature.
  3. Flue gas should be no more than 50°F above return temperature.
  4. If the difference is higher, clean the heat exchanger (see maintenance, p. 151).
  5. If the flue temperature is higher still, shut down, let cool, and clean the heat exchanger.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.