Weil-McLain Boiler: Connect gas supply piping to boiler
Connect gas supply piping to boiler on a Weil-McLain boiler: Gas connection is ½ in. NPT male on top of the boiler. Installer supplies the shut-off valve and fittings.
Applies to: ECO Tec Series 3 all models
How to fix connect gas supply piping to boiler: step by step
- Use a pipe wrench on the gas line at the top of the boiler while tightening the gas line assembly to the boiler connection.
- Use two wrenches when tightening gas piping at the boiler so the boiler gas connection does not turn.
- Install steel pipe fittings per Figure 74 with a manual gas shut-off valve, union, and drip leg (tee, 4 in. nipple, cap).
- Apply pipe dope sparingly to male threads only, and use pipe dope compatible with propane.
- In Canada, identify the manual gas shut-off valve.
- Support gas piping with hangers, not by the boiler or its accessories.
- Purge all air from the gas supply piping.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.