Weil-McLain Boiler: Install propane orifice (Ultra-80, -105, -155, -230, -299)
Install propane orifice (Ultra-80, -105, -155, -230, -299) on a Weil-McLain boiler: Swap the natural gas orifice for the propane orifice at the gas valve. Isolate the boiler first and cool it if it has been running.
Applies to: Ultra-80, Ultra-105, Ultra-155, Ultra-230, Ultra-299
How to fix install propane orifice (ultra-80, -105, -155, -230, -299): step by step
- Turn off electrical supply and close the external manual gas shut-off valve.
- Allow the boiler to cool if it has been operating.
- Take the orifice disc from the conversion kit and check the stamping matches the model size.
- Remove the jacket front door (two screws at lower front).
- Remove the air inlet silencer from the adapter.
- Disconnect the gas valve electrical plug.
- Remove the four screws holding the gas valve inlet adapter to the valve.
- Remove the three Allen-head screws holding the gas valve to the venturi using a 5 mm wrench.
- Place the orifice in the black rubber grommet in the gas valve side and secure it.
- Check the O-ring between the gas valve and inlet adapter. It must be in good condition and installed.
- Reposition the gas valve on the venturi and install the three Allen-head screws.
- Secure the inlet adapter to the valve with four screws. On Ultra-80 and -105, make sure the plastic hose runs from the gas valve to the inlet elbow.
- Reconnect the gas valve electrical plug.
- Reattach the air inlet silencer.
- Attach the propane conversion label next to the rating plate.
- Reinstall the boiler door.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 48-49. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.