Weil-McLain Boiler: Manifolded combustion air for multiple boilers
Manifolded combustion air for multiple boilers on a Weil-McLain boiler: Several boilers may share one combustion air duct, but vent pipes must never be combined.
Applies to: Multiple Ultra boilers using a common combustion air manifold
How to fix manifolded combustion air for multiple boilers: step by step
- Only air piping may be combined. Do not combine vent piping; flue gas leakage and component damage can occur.
- Each boiler must have its own individually routed and terminated vent.
- Size the duct: minimum area in square inches = total MBH input divided by 2 (example: six Ultra-155 = 930 MBH, minimum 465 sq in).
- Provide at least 1 sq in of free area per 2,000 Btuh total input, adjusted for louver restriction.
- Keep 12 in minimum above grade or snow line, and at least 3 ft below any vent termination within 10 ft.
- If a combustion air damper is used, wire it so the boilers cannot fire until the damper is open.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.