Weil-McLain Boiler: Route condensate drain tubing

Updated · by Aurora Star Tech Inc.

Route condensate drain tubing on a Weil-McLain boiler: The drain line must stay open and unobstructed. A frozen or blocked line can spill condensate and cause water damage.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All Ultra models

Common causes of route condensate drain tubing

  • Condensate freezes in the line
  • Line is obstructed

How to fix route condensate drain tubing: step by step

  1. Connect the drain tubing to the 1/2 in PVC tee and run it to a floor drain or condensate pump.
  2. Use 1/2 in PVC or CPVC, or 5/8 in I.D. tubing, and use materials approved locally. In Canada, use CSA or ULC certified pipe and fittings.
  3. Leave the top of the 1/2 in tee open as a vacuum break.
  4. If using a pump, choose one approved for condensing boilers and furnaces, with an overflow switch.
  5. When sizing the pump, include the total load of all Ultra boilers connected to it.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Ultra Series 4 boiler manual, p. 28. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.