Weil-McLain Boiler: Closed-type expansion tank piping
Closed-type expansion tank piping on a Weil-McLain boiler: Air is in direct contact with the tank water in this layout. Never use an automatic air vent with a closed-type tank, because it removes air and water-logs the tank.
Applies to: Closed-type expansion tank (Figure 67)
Common causes of closed-type expansion tank piping
- Automatic air vent fitted to a closed-type tank system
- Leaks in system or tank piping
How to fix closed-type expansion tank piping: step by step
- Run ½" or ¾" piping from the air separator outlet to the tank fitting.
- Slope horizontal piping at least 1 inch per 5 feet.
- Use a tank fitting such as B&G Tank-trol or Taco Taco-trol to control gravity flow and set fill height.
- Do not install an automatic air vent in this system.
- Correct all leaks in the system or tank piping.
- Fill the tank per the tank maker's instructions.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.