Weil-McLain Boiler: Cooling down and draining before servicing the brazed plate heat exchanger
Cooling down and draining before servicing the brazed plate heat exchanger on a Weil-McLain boiler: Let the brazed plate exchanger cool before opening it, since water inside may still be hot and can cause severe injury.
Applies to: 80/110/150/199 Series 3
How to fix cooling down and draining before servicing the brazed plate heat exchanger: step by step
- Shut off the gas supply at the boiler manual gas valve, but leave power on.
- Run cool domestic water through the boiler by opening a hot fixture. The boiler will lock out on ignition fault, but the internal circulator keeps running to cool components.
- Once components are cool, turn off all electrical power to the boiler.
- Close the domestic cold water inlet isolation valve.
- Release DHW pressure by opening a hot tap downstream of the boiler, then open the DHW drain valves.
- Close the space heating supply and return valves (Boiler Out and Boiler In).
- Release boiler pressure by operating the relief valve or opening the boiler drain, and drain both boiler in and boiler out.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 156. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.