Weil-McLain Boiler: Zone valve zoning, variable primary flow with DHW
Zone valve zoning, variable primary flow with DHW on a Weil-McLain boiler: Variable flow system with optional DHW piping shown in Figure 17.
Applies to: SVF 1500-3000 Series 1
How to fix zone valve zoning, variable primary flow with dhw: step by step
- Install a system circulator sized for the variable flow and head.
- Install a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
- Optionally add a bypass with a differential pressure valve between near-boiler supply and return. If used, place the System Supply sensor after the bypass.
- Install a flow switch if system flow could fall below the minimum flow in Figure 10.
- Connect DHW secondary connector piping no more than 8 pipe diameters apart.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.