Weil-McLain Boiler: Diaphragm or bladder expansion tank piping and pressure
Diaphragm or bladder expansion tank piping and pressure on a Weil-McLain boiler: Size the tank for boiler and system water volume and temperature. Undersized tanks lose water through the relief valve and add make-up water, which can eventually fail the boiler.
Applies to: Diaphragm or bladder type expansion tank (Figure 66)
Common causes of diaphragm or bladder expansion tank piping and pressure
- Undersized expansion tank
- Tank air charge not matched to cold fill pressure
How to fix diaphragm or bladder expansion tank piping and pressure: step by step
- Locate the air separator and expansion tank as shown on pages 60 to 62.
- Always locate the cold-water fill connection at the expansion tank.
- Calculate cold fill pressure and set the tank air charge to the same value, checking with the tank removed from the system.
- Confirm operating pressure after heat expansion stays at or below 24 PSIG.
- Install an automatic air vent on top of the air separator per the separator instructions.
- Add extra tanks by tying them into system tees if more expansion volume is needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.