Weil-McLain Boiler: Install vertical direct vent with separate pipes

Updated · by Aurora Star Tech Inc.

Install vertical direct vent with separate pipes on a Weil-McLain boiler: Air and vent pipes run up through the roof with separate penetrations. The air inlet must sit well below the vent outlet and well above the roof or snow line.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vertical direct vent, separate pipes

How to fix install vertical direct vent with separate pipes: step by step

  1. Check the roof location against the clearance figure before cutting.
  2. Use only listed vent materials and adapters. Stay within the maximum pipe lengths.
  3. Cut the air and vent penetrations, spacing them no closer than the minimum shown. Install a corrosion-resistant thimble in the vent hole.
  4. Fit flashing and sealing boots sized for each pipe, following the vent maker's instructions.
  5. Fit bird screens to the air and vent terminations. Screens are bought separately.
  6. Air pipe ends in a 180-degree return bend or down-turned elbow at least 12 in above the roof or snow line.
  7. Vent pipe ends in an up-turned coupling at least 12 in above the air intake.
  8. Slope horizontal piping down toward the boiler at least 1/4 in per foot.
  9. Support pipe every 5 ft on horizontal and vertical runs, with a hanger within 6 in of any upturn.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec Series 3 boiler manual, p. 39-40. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.