Weil-McLain Boiler: Sizing combustion and ventilation air openings
Sizing combustion and ventilation air openings on a Weil-McLain boiler: Openings are sized in free area after louver losses. A single opening may be used if it starts within 12 in of the ceiling and meets the clearance and direct-to-outdoors rules. Its free area must equal at least the sum of all vent connectors in the space and at least 1 sq in per 3000 Btuh of input. In tight construction, use two openings (one within 12 in of the ceiling, one within 12 in of the floor) at 1 sq in per 1000 Btuh of all appliances. No openings are needed if the space volume is at least 50 cu ft per 1000 Btuh of all installed appliances, and the building is not tight construction.
Applies to: Boiler room air supply
Common causes of sizing combustion and ventilation air openings
- Space under negative pressure from exhaust fans or air movers
- Motorized air damper fails to open or closes during firing
How to fix sizing combustion and ventilation air openings: step by step
- Sum the input of all appliances in MBH and check the opening or volume requirement.
- Size the opening free area for the vent connectors and the input rating.
- If a motorized damper is used, interlock it so the boiler will not fire unless it is fully open.
- Wire an isolated proving contact for the damper in series with the thermostat input so the boiler shuts down if the damper closes.
- Make sure the space is never under negative pressure.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 Boiler Manual, pp. 13-14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.