Weil-McLain Boiler: Example C shadow boiler field wiring (Shadows 2 to 4)
Example C shadow boiler field wiring (Shadows 2 to 4) on a Weil-McLain boiler: Shadow 2 serves Zones 3 to 6 with Circulators 3 to 6. Shadow 3 serves Zones 7 to 10 with Circulators 7 to 10. Shadow 4 serves Zones 11 to 14 with Circulators 11 to 14. Each boiler has its own 120 VAC supply and boiler circulator. Each output is rated 2.0 A max.
Applies to: Example C shadow boilers 2, 3 and 4
How to fix example c shadow boiler field wiring (shadows 2 to 4): step by step
- Wire each shadow boiler to 120 VAC power on L1.
- Wire each shadow boiler circulator to BOILER PUMP and its 2-pin plug at J4-4.
- Wire each zone circulator to its numbered output, rated 2.0 A max.
- Wire each zone thermostat to its W, R and C terminals.
- Wire the outdoor air and system sensors to J19 on each shadow boiler; sensors marked with an asterisk are for redundancy only.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 29-30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.