Weil-McLain Boiler: Multiple boilers with an isolation heat exchanger: when to use it
Multiple boilers with an isolation heat exchanger: when to use it on a Weil-McLain boiler: Use an isolation heat exchanger for large systems with high mineral content in the water, systems fed with untreated makeup water, old systems heavily scaled or rusted inside piping and heat units, process applications, commercial service water, and high-pressure systems that need a heating-system relief setting above 30 PSIG (tall buildings).
Applies to: Multiple Ultra boilers on isolation heat exchanger piping
How to fix multiple boilers with an isolation heat exchanger: when to use it: step by step
- Size the heat exchanger with the exchanger manufacturer.
- Pipe the exchanger shell side and tube side per the manufacturer. Tube-side flow and temperature must meet the heating system requirements.
- Give the heat exchanger shell-side circuit its own expansion tank.
- Give the heating system circuit its own expansion tank and its own relief valve, set to protect the system and the exchanger piping.
- Strap supply and return sensors to the lines at least 6 pipe diameters, but no more than 3 feet, from the boiler connection tees.
- Install a flow/check valve and boiler circulator on each boiler, and run each boiler relief valve discharge per the Ultra boiler manual.
- If individual isolation valves are used, individual boiler level controls may be needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.