Weil-McLain Boiler: Install the heating relief valve
Install the heating relief valve on a Weil-McLain boiler: Relief valve goes on the top boiler water pipe only, never on the boiler outlet. Discharge must be routed safely.
Applies to: Heating side relief valve
How to fix install the heating relief valve: step by step
- Mount the relief valve after the hydrostatic test is complete, not before.
- Install it in a ¾" street elbow with a ¾" tee on the top water pipe (air elimination/relief connection).
- Keep the spindle vertical and locate the valve above the heat exchanger.
- Do not place any shutoff valve between the relief valve and the boiler or in the discharge line.
- Pipe the discharge to a safe place, short and the same size as the valve outlet, pitched downward.
- End the discharge plain, not threaded, in material rated for 375°F or greater, at least 6 inches above a floor drain where it is visible.
- Do not run discharge where freezing can occur.
- After filling and pressurizing, lift the lever to test. Replace the valve if it does not discharge freely.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 18 reference, 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.