Weil-McLain Boiler: Checking a damper output during a boiler call
Checking a damper output during a boiler call on a Weil-McLain boiler: Use this when a combustion air damper, flow switch or interlock output does not act the way the boiler should during a call for heat. The output's timing depends on whether it is set as a system or local damper.
Applies to: Evergreen Pro Series 2 boilers, damper and interlock outputs
Common causes of checking a damper output during a boiler call
- Damper option set to SYSTEM DAMPER when LOCAL DAMPER is needed, or the reverse
- Wrong priority or input assigned to the output
- Burner not firing, so the output never energizes
How to fix checking a damper output during a boiler call: step by step
- Confirm which damper option (SYSTEM or LOCAL) is assigned to the output being checked.
- With no call for heat, confirm the output is off.
- On a call, check that a SYSTEM DAMPER output energizes when the boiler starts pre-purge.
- Check that a LOCAL DAMPER output only energizes if this boiler is trying to fire.
- After the burner shuts off, confirm the output drops once post-purge is complete.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Series 2 Advanced Manual 550-100-581, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.