Updated · by Aurora Star Tech Inc.

Remove boiler from an existing common vent and test the remaining appliances on a Weil-McLain boiler: The Ultra boiler cannot be common vented with any other appliance. When an old boiler is replaced, the remaining appliances on the old common vent must be checked to confirm they still vent safely.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Existing common vent systems with appliances left connected after boiler replacement

Common causes of remove boiler from an existing common vent and test the remaining appliances

  • Common vent may be too large for the remaining appliances
  • Blocked, leaking, corroded or unpitched vent
  • Spillage at the draft hood relief opening

How to fix remove boiler from an existing common vent and test the remaining appliances: step by step

  1. Visually inspect the existing vent for proper size, horizontal pitch, blockage, restriction, leakage and corrosion.
  2. Close building doors and windows between the appliance space and other spaces. Turn on clothes dryers, exhaust fans and any non-vented appliances. Run range hoods and bathroom exhausts at maximum. Do not run a summer exhaust fan. Close fireplace dampers.
  3. Operate the appliance being tested alone, with the other appliances off. Follow its lighting instructions and set the thermostat so it runs continuously.
  4. After 5 minutes of main burner operation, test the draft hood relief opening for spillage with a match, candle or smoke.
  5. When each appliance passes, return doors, windows, fans, dampers and other gas appliances to their previous use.
  6. If the vent does not pass, correct it so it conforms to the National Fuel Gas Code, ANSI Z223.1, or B149.1/B149.2 in Canada. This may mean resizing the vent toward the minimum size from the code tables.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 boiler manual, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.